Technical Specifications
Overview
Professional Transformer Analysis
This versatile analyzer is engineered for comprehensive testing of both Current Transformers (CT) and Potential Transformers (PT). It supports a wide array of diagnostic functions including excitation curve analysis, turns ratio testing, polarity checks, and coil resistance measurements. Built for field use, the device combines high-precision measurement capabilities with a rugged, portable design, making it an essential tool for electrical power testing and maintenance.
Key Performance Metrics
Maximum Knee Voltage
Power Output
Standards & Compliance
- Supported Standards
- IEC60044-1IEC60044-6GB1208GB16847C57.13
Technical Specifications
CT Testing Capabilities
- Excitation curve and parameters
- Turns ratio
- Ratio and phase error
- Polarity mark check
- Coil resistance measurement
- Secondary loop burden measurement
- Error line curve test (protection CT)
- Transient CT parameters
- CT nameplate guess
- Saturation hysteresis loop
PT Testing Capabilities
- Turns ratio
- Phase angle error
- Polarity test
- Secondary burden test
- Coil resistance test
- PT routine test
Electrical Ratings
- Power Supply
- AC220V±10%, 50Hz/60Hz±10%
- Current Output
- 0.001~5A (RMS)
Measurement Accuracy
Measurement Ranges & Accuracy
| Parameter | Range | Accuracy Note |
|---|---|---|
| Current | 0~10A | <±0.1%+0.01%FS |
| Voltage | 0~200V | <±0.1%+0.01%FS |
| Coil Resistance | 0~8kΩ | <0.2%RDG+0.02%FS |
| Phase | - | ±2min (0.01min res) |
Physical Characteristics
Operating Conditions
- Dimensions
- 485mm × 356mm × 183mm
- Weight
- 15 kg