Generator Busbar Synchronization Meter
Synchronization meter designed for generator and bus bar synchronization. It features adjustable delay, phase difference (Δφ), and voltage difference (ΔU) settings.




Technical Specifications
Product Overview
Advanced Synchronization Monitoring
The SQ0214 is a microprocessor-based synchronising unit designed to measure phase differences between a bus bar and a generator. It supports both manual and semi-automatic synchronization installations, serving as a versatile replacement for dual voltmeters and dual frequency-meters. The integrated LCD provides real-time monitoring of voltage and frequency for both the generator and bus bar, while the LED circular display offers immediate visual feedback on phase alignment.
Technical Specifications
- Standard Phase Resolution
- 20 °el
- Sync Range Phase Resolution
- 5 °el
- Adjustable Delay
- 0.1 to 1.0 seconds
- Phase Difference Adjustment
- 2 to 20 ± degrees
- Voltage Difference Adjustment
- 1 to 10 ± Un%
Compliance and Safety
- Safety Category
- CAT III
- Maximum Input Voltage
- 400 V
- Auxiliary Power Input
- 24 V
Display Features
Measurement Parameters
- Generator Voltage (UGEN)
- Bus-bar Voltage (UBB)
- Generator Frequency (FGEN)
- Bus-bar Frequency (FBB)
- Phase Difference (Δφ)
- Key Indicators
- 24 LED circular displayBacklit LCDSync status indicator