275kVA 220kW 50Hz Silent Diesel Generator
This 275kVA silent diesel generator delivers 220kW of power at 50Hz. Enclosed in a soundproof canopy, it ensures quiet operation for various industrial and commercial needs.





Technical Specifications
Overview
High-Performance Silent Power Solution
This 275kVA/220kW diesel generator is engineered for reliable standby and prime power in noise-sensitive environments. Featuring a robust silent canopy made of high-quality, corrosion-resistant sheet metal, it ensures high waterproof and dust-proof performance for outdoor use. Designed for versatility, the unit includes integrated crane and forklift points for easy transportation and a large fuel tank supporting over 8 hours of continuous operation.

Key Performance Metrics
Performance Highlights
Engine Specifications
Engine Details
| Parameter | Specification |
|---|---|
| Cylinders | 6 / In-Line |
| Cycle | 4-Stroke |
| Bore / Stroke | 114 mm / 145 mm |
| Induction | TCA |
| Cooling Method | Water Cooled |
| Displacement | 8.9 L |
| Compression Ratio | 16.6:1 |
| Governing Type | Electronic |
| Lubricant Capacity | 27.6 L |
| Coolant Capacity | 11.1 L |
Alternator & Control
Electrical & Alternator
- 100% Copper Windings
- Insulation Class: H
- Voltage Regulation: ±1.0%
- Protection Class: IP23
- Excitation System: Self-excited SHUNT
- Winding Pitch: 2/3
- Standard Underspeed Protection
Operational Features
- Protection & Control
- Low Oil Pressure ProtectionOvervoltage ProtectionOverspeed ProtectionOverload ProtectionShort-circuit ProtectionHigh Temperature ProtectionRS232/RS485 InterfaceOptional ATS Support

Physical & Environmental
Physical Characteristics
| Type | Dimensions (L*W*H) | Weight |
|---|---|---|
| Open Set | 2550 x 960 x 1630 mm | 1850 kg |
| Soundproof Set | 3530 x 1150 x 1900 mm | 2550 kg |
- Noise Level (at 7m)
- 78 dBA
Applications
Recommended Industries
Quality & Compliance
- Standards & Certifications
- ISO 9001:2008ISO 14001:2004OHSAS 18001:2007CE Machinery SafetyLow Voltage DirectiveEMC CompatibilityOutdoor Use 2005/88/EC
- Pre-Delivery Testing
- 1-hour full load test at 25%, 50%, 75%, 100%, and 110% capacity.