2000kVA Resistive Reactive Load Bank
This load bank features a compact and lightweight design, making it ideal for transport between job sites. It provides intelligent operator controls, safety indication layouts, and adjustable load step resolution for scheduled maintenance and testing of power systems.




Technical Specifications
Overview
High-Capacity Testing Solution
This 2000kVA Resistive Reactive Load Bank is designed for rigorous testing and performance verification of high-power UPS systems, inverters, and diesel generator sets. It provides a comprehensive solution for both resistive and inductive load testing, utilizing a modular design for simple operation and maintenance. Built for durability, the unit features forced air cooling and automatic overheating protection, making it a reliable choice for telecom, electric power, and industrial manufacturing applications.
Performance Metrics
Rated Power Capacity
- Load Tolerance
- ±5% per step, ±3% overall
- Power Factor
- 0.8 (lag) to 1
Technical Specifications
Protection Grade
- Rated Voltage/Frequency
- 400V, 3 phase 4 wire, 50Hz
- Cooling System
- Forced air cooling via axial fan; horizontal inlet, vertical exhaust
- Insulation Class
- F
- Duty Cycle
- Continuous
Control & Connectivity
- Control Modes
- Local Panel ControlSoftware Remote Control
- Communication Interfaces
- RS485RS232
Physical Characteristics
- Dimensions
- 4000mm x 2350mm x 2591mm
- Weight
- 7900 kg
- Enclosure Type
- Container type with ladder, mesh air inlets/outlets, and protection doors
Operating Environment
Ambient Conditions
| Parameter | Range |
|---|---|
| Ambient Temperature | -20℃ to +50℃ |
| Relative Humidity | ≤95% |
| Atmospheric Pressure | 86 to 106 kPa |